Fluke 1623-2 GEO Earth Ground Resistance Meter
Please select an item in the list...
{{details.product.PriceUnits}}
Please fill out this field...
Please enter a number...
Please enter at least 1...
Please enter at max 999999...

You purchased this item on {{details.product.OrderHistory[0].OrderDate | date : 'yyyy-MM-dd'}}

Personal Greeting

Fluke 1623-2 Basic Kit II Geo Earth Ground Tester LIMITED STOCK going for R32 990 Ex VAT

Fluke 1623-2 Earth Ground Tester performs all four ground tests quickly and accurately.

The Fluke 1623-2 earth ground tester measures earth ground loop resistances using only clamps, only stakes, or one clamp and stakes. With the stakeless test method, the Fluke 1623-2 is able to measure earth ground loop resistances for multi-grounded systems using only current clamps. This technique eliminates the dangerous, and time-consuming job of disconnecting parallel grounds, and finding suitable locations for auxiliary ground stakes. You can use it to perform earth ground tests in places you’ve not considered before, such as inside buildings, on power pylons, or anywhere you don’t have access to soil.

Keep your options open

Keep in mind, the stakeless test method works only if a bonded earth ground system exists for the building or structure under test. If there is only one path to ground, typical with many residential applications, you will need to use the fall-of-potential test method that requires stakes.

The 1625-2 is also very easy to use. World class accessories speed set up and test time. And the tester tells you which stakes or clamps to connect for each test. The large rotary switch and buttons are easy to operate even with a gloved hand. And you can store up to 1,500 records and access them easily via the USB port.

Fluke 1623-2 GEO Earth Ground Tester Kits

The Fluke 1623-2 GEO Earth Ground Tester offers data storage and download capabilities via USB port. World-class accessories will simplify and speed up testing time.

Fluke 1623-2-Kit GEO Earth Ground Tester summary

  • 3- and 4-pole Fall-of-Potential, earth resistance loop testing
  • 4-pole Soil Resistivity testing
  • Selective earth ground rod testing using 1 clamp
  • Stateless earth ground rod testing using 2 clamps
  • IP56 rated for outdoor use
  • Rugged carrying case
  • USB data storage and transfer

Fluke 1623-2 Basic Kit Geo Earth Ground Tester, Kit / no clamps

  • 3- and 4-pole Fall-of-Potential, earth resistance loop testing
  • 4-pole Soil Resistivity testing
  • IP56 rated for outdoor use
  • Rugged carrying case
  • USB data storage and transfer

Need even more accuracy? Check out the 1625-2 that offers:

  • Automatic Frequency Control identifies existing interference and chooses a measurement frequency to minimize its effect, thus providing a more accurate earth ground value.
  • R* measurement that calculates earth ground impedance at 55 Hz to more accurately reflect the earth ground resistance that a fault-to earth ground would see.

Other useful capabilities:

  • Includes USB port for data storage and transfer
  • Works with world-class that speed set up and test time
  • Comes with a rugged carrying case
  • A unique earth ground tester that performs fast, accurate testing with and without stakes
  • Tests 3- and 4-pole fall-of-potential, and 4-pole soil resistivity (with stakes)
  • Performs selective earth ground rod testing (one clamp + stakes)
  • Performs stakeless earth ground rod testing (two clamps)
  • Features IP56 rating for outdoor use
General Specifications
Display: 1999 digit LCD Display with special symbols, digit height 25 mm, fluorescent backlight
User interface Instant measurement through TURN and START one button concept. The only operating elements are rotary switch and START button
Robust, water and dust resistant Instrument is designed for tough environmental conditions (rubber protective cover, IP56)
Memory Internal memory storage up to 1500 records accessible via USB port
Temperature Range
Operating temperature -10°C to 50°C (14°F to 122°F)
Storage temperature -30°C to 60°C (-22°F to 140°F)
Temperature coefficient ±0.1% of reading/°C < 18°C > 28°C
Intrinsic error Refers to the reference temperature range and is guaranteed for 1 year
Operating error Refers to the operating temperature range and is guaranteed for 1 year
Climatic class C1 (IEC 654-1), -5°C to +45°C (23° to +115° F), 5% to 95% RH
Protective type IP56 for case, IP40 for battery door according to EN60529
Safety Protection by double and/or reinforced insulation. max. 50 V to earth. IEC61010-1: Pollution degree 2
EMC (emission immunity) IEC61326-1: Portable
Quality system Developed, designed and manufactured according to DIN ISO 9001
External voltage V ext, max = 24 V (DC, AC < 400 Hz), measurement inhibited for higher values
V ext rejection > 120 dB (162⁄3, 50, 60, 400 Hz)
Measuring time Typical 6 seconds
Max. overload 250 V rms (pertains to misuse)
Auxiliary power 6 x 1.5 V Alkaline (type AA LR6)
Battery life span Typical > 3,000 measurements
Dimensions (W x H x D) 250 x 133 x 187 mm (9.75 x 5.25 x 7.35 in)
Weight 1.1 kg (2.43 lb) including batteries
7.6 kg (16.8 lb) incl. accessories and batteries in carrying case
RA 3-Pole Ground Resistance Measurement (IEC 1557-5)
Switch position RA 3-pole
Resolution 0.001 Ω to 10 Ω
Measuring range 0.020 Ω to 19.99 kΩ
Accuracy ±(2% rdg + 3 d)
Operating error ±(5% rdg + 3 d)
Measuring Principle: Current/Voltage Measurement
Measuring voltage Vm = 48 V AC
Short-circuit current > 50 mA
Measure frequency 128 Hz
Probe resistance (RS) Max 100 kΩ
Auxiliary earth electrode resistance (RH) Max 100 kΩ
Additional error from RH and RS RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2%
Monitoring of RS and RH with error indicator.
Automatic range selection.
Measurement is not performed if the current through the current clamp is too low.
RA 4-Pole Ground Resistance Measurement (IEC 1557-5)
Switch position RA 4-pole
Resolution 0.001 Ω to 10 Ω
Measuring range 0.020 Ω to 19.99 kΩ
Accuracy ±(2% rdg + 3 d)
Operating error ±(5% rdg + 3 d)
Measuring Principle: Current/Voltage Measurement
Measuring voltage Vm = 48 V AC
Short-circuit current > 50 mA
Measure frequency 128 Hz
Probe resistance (RS + RES) Max 100 kΩ
Auxiliary earth electrode resistance (RH) Max 100 kΩ
Additional error from RH and RS RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2%
Monitoring of RS and RH with error indicator.
Automatic range selection.
RA 3-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp )
Switch position RA 3-pole with clamp
Resolution 0.001 Ω to 10 Ω
Measuring range 0.020 Ω to 19.99 kΩ
Accuracy ±(7% rdg + 3 d)
Operating error ±(10% rdg + 5 d)
Measuring Principle: Current/Voltage Measurement (with External Current Clamp)
Measuring voltage Vm = 48 V AC
Short-circuit current > 50 mA
Measure frequency 128 Hz
Probe resistance (RS) Max 100 kΩ
Auxiliary earth electrode resistance (RH) Max 100 kΩ
Monitoring of RS and RH with error indicator.
Automatic range selection.
Measurement is not performed if the current through the current clamp is too low.
RA 4-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp )
Switch position RA 4-pole with clamp
Resolution 0.001 Ω to 10 Ω
Measuring range 0.020 Ω to 19.99 kΩ
Accuracy ±(7% rdg + 3 d)
Operating error ±(10% rdg + 5 d)
Measuring Principle: Current/Voltage Measurement (with External Current Clamp)
Measuring voltage Vm = 48 V AC
Short-circuit current > 50 mA
Measure frequency 128 Hz
Probe resistance (RS) Max 100 kΩ
Auxiliary earth electrode resistance (RH) Max 100 kΩ
Monitoring of RS and RH with error indicator.
Automatic range selection.
Measurement is not performed if the current through the current clamp is too low.
Stakeless Ground Loop Measurement (2 Clamps)
Switch position RA 4-pole 2 clamps
Resolution 0.001 Ω to 10 Ω
Measuring range 0.020 Ω to 19.99 kΩ
Accuracy ±(7% rdg + 3 d)
Operating error ±(10% rdg + 5 d)
Measuring Principle: Stakeless Measurement of Resistance in Closed Loops Using Two Current Transformers
Measuring voltage Vm = 48 V AC
Measure frequency 128 Hz
Noise current (IEXT) Max. IEXT = 10 A (AC) (RA < 20 Ω)
Max. IEXT = 2 A (AC) (RA > 20 Ω)
Automatic range selection.
The information regarding stakeless ground loop measurements is only valid when used in conjunction with the recommended current clamps at the minimum distance specified.

Fluke 1623-2

Fluke 1623-2 GEO Earth Ground TesterBuy it Includes: GEO Earth Ground Tester User's Manual Batteries Quick Reference Guide 2 Test Leads USB Cable
 

Fluke 1623-2-Kit GEO Earth Ground Tester summary

  • GEO Earth Ground Tester
  • User’s Manual
  • Batteries
  • Quick Reference Guide
  • USB Cable
  • 2 Clamps
  • C1620 Professional Carrying Case
  • 4 Earth Ground Stakes
  • 3 Cable Reel

Fluke 1623-2 Basic Kit Geo Earth Ground Tester, Kit / no clamps - II

  • GEO Earth Ground Tester
  • User’s Manual
  • Batteries
  • Quick Reference Guide
  • USB Cable
  • C1620 Professional Carrying Case
  • 4 Earth Ground Stakes
  • 3 Cable Reel